Permit Number: T14CM08368
Parcel: 10408092B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T14CM08368
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Detail 5/A5, 90 degree turn landing needs 5' x 5' clearance as per 2009 ICC A117.1, Sectiobn 504.7.
2. New parts counter non compliant:
a. needs accessible counter as per ICC A117.1, Section 904.3
b. Needs turn around clearances as per ICC A117.1, Section 304.2.
3. Counter detail 7/A9 is not included in this submittal. Please submit for review and compliance.
4. What has changed in touilet room detail 1/A5?
a. Whare is elevation sheet A9?
b. Provide set of orignally approved set of documents.
END OF REVIEW
04/15/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
04/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2015 AROMERO4 APPROVAL SHELF Completed
04/15/2015 AROMERO4 OUT TO CUSTOMER Completed