Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM08368
Parcel: 10408092B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08368
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM08368

2012 IECC (interior) lighting calculation: provide ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
01/08/2015 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Jim Click Chrysler - Expansion
T14CM08368
Building Plan (1st Review)

TRANSMITTAL DATE: January 5, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until development package DP14-0225 has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/14/2015 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/17/2014 MARTIN BROWN FIRE REVIEW Approved
12/17/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET T1
1. Building Code Analysis:
a. Please provide square footage analysis as follows:
1. Demolished Building; conditioned spaces only 2. Demolished canopies
3. Existing remodeled
1st Level
2nd Level
4. Addition
1st Level
2nd Level
---------------------------------------------------------------------------
Totals 1st Level
2nd Level
----------------------------------------------------------------------------
Gross total Building Gorss total Canopies
2. Please provide an exiting plan and show any fire rated partitions required.
3. Provide a complete occupant load summary and analysis. Summarize the different building use occupancy loads.
4. Provide a complete toilet fixture analysis based upon the calculated occupancy load.
a. The one lavatory per toilet room appears light. Please verify.
SHEET A1.1
5. At the ramp from the Customer Service to the the Show Room:
a. Provide a large scale plan details showing all accessible requirements such as dimensioning, slopes, grade differences, ramp run, landings and handrails. Provide a handrail elevation.
b. Fill in the section reference mark
SHEET A5
6. At detail 1:
a. Reference the sheet number for the toilet room accessory schedule.
b. Both entrance doors are non-compliant with the 2009 ICC A117.1, Section 404.2.3 (f).
SHEET A9
7. Finish this sheet.
SHEETS S2.1 AND S2.2
8. Calcs call for J3 to be 2 x 8s. There are no 2x8s on Joist Schedule.
9. Detail 203, call out beam as MC18 x 42.7.
SHEET S1.2
10. Provide certification for special inspectors as outlined on this sheet and others.
11. Provide new roof top mounted HVAC roof load calculations for both new and existing framing.
END OF REVIEW
12/19/2014 LOREN MAKUS ENGINEERING REVIEW Approved DP must be approved first.
12/29/2014 ROBERT SHERRY WATER REVIEW Completed
12/30/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Revise the water distribution system design criteria to account for the actual static lift to the highest fixture (e.g. the sink on the second floor). Reference: Section 604.1, IPC 2012, as amended by the City of Tucson.
3. Provide a water pressure regulator conforming to ASSE 1003 or CSA B356 to limit the water pressure to 80 PSI or less. Revise the water pressure calculations as required. Reference: Section 604.8, IPC 2012 and Section E103.3 (1), Appendix E, IPC 2012.
4. Verify that the roof drains used for the secondary (overflow) roof drainage system conform to ASME A112.6.4 0r ASME A112.3.1 (See detail 4/A8). Reference: Section 1102.6, IPC 2012.
5. The two low roof sections located between columns 9 and 10 and between columns D and K are noted as each having only 640 square feet of roof to drain but the overflow from the two adjacent roof sections (each with 2164 square feet) should be included when sizing the drain sizes for the two low roof sections. On sheet P2.2, one set of roof/overflow drains is called out as being 4" in size and the other set of roof/overflow drains is called out as being 3" in size but on sheet P1.1 both sets are labeled as being 3" in size. Also, with a total drainage area of 2804 square feet and a slope of ΒΌ" per foot, each of the horizontal storm drain pipes must be at least 4" in diameter. Reference: Sections 1106.2 and 1106.3, IPC 2012.
6. Provide roof drainage and hydraulic size calculations for the overflow scuppers based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1101.7, 1106.1, 1106.4, and 1108.3, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
12/30/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
3. Show that the mechanical systems for the building comply with the current energy code, i.e. provide the COMcheck Mechanical Compliance Certificate. Reference: Section C403.1, IECC 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
5. Show how the "Additional Efficiency Package Requirements" noted in Section C406, IECC 2012 is to be addressed for the building additions. Reference: Sections C101.4.3 and C401.2.1, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2015 FERNE RODRIGUEZ APPROVAL SHELF Completed
01/28/2015 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
01/28/2015 CPIERCE1 REJECT SHELF Completed