Permit Number: T14CM08365
Parcel: 104080870

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM08365
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2015 STEVE SHIELDS ZONING REVIEW Reqs Change
06/25/2015 LOREN MAKUS ENGINEERING REVIEW Approved
07/13/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN
REVIEW COMMENTS
Date: 7-13-15
Activity: T14CM08365
Address: 850 W. Auto Mall Dr
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet T1
1. Please include sheet A4.3 on sheet index.
2. Square footage areas indicated on occupant load calculations are not consistent with the proposed addition area. Please provide an accurate occupant load calculation that includes the proposed service area and adjust the occupant loads accordingly, 1004, 2902.

If you have any questions please contact:

Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
07/14/2015 AROMERO4 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify how the new occupiable area for the canopy area has been determined. If you have ever waited for service under one of those canopies, you know it is an occupiable area (albeit not necessarily 100 square feet per person). Aside from the number of occupants, the fixture calculations are incorrect. Assuming 110 total people inn the B occupancy (55 of each sex), three water closets and 2 lavatories are required for each sex. [Initial comment: The number of required fixtures shown in Table 2902.1, IBC 2012 is based upon the minimum fixtures required for each person or fraction of the number of persons. Since fractional fixtures cannot be installed, fractional numbers for fixtures shall also be rounded up to the next whole number. Increase the number of required lavatories to 3 lavatories in each restroom. Reference: footnote (a), Table 2902.1, IBC 2012.]
2. See the new comment above. [Initial comment: No more than 50% of the required water closets in a restroom may be substituted with urinals. Reference: Section 419.2, IPC 2012.]
07/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2015 AROMERO4 APPROVAL SHELF Completed
07/14/2015 AROMERO4 OUT TO CUSTOMER Completed