Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T14CM08365
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide an updated Envelope Compliance Certificate to demonstrate energy code compliance for the alterations to the building envelope. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. |
| 06/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The number of required fixtures shown in Table 2902.1, IBC 2012 is based upon the minimum fixtures required for each person or fraction of the number of persons. Since fractional fixtures cannot be installed, fractional numbers for fixtures shall also be rounded up to the next whole number. Increase the number of required lavatories to 3 lavatories in each restroom. Reference: footnote (a), Table 2902.1, IBC 2012. 2. No more than 50% of the required water closets in a restroom may be substituted with urinals. Reference: Section 419.2, IPC 2012. |
| 06/10/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/16/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/18/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/18/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 06/18/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |