Permit Number: T14CM08229
Parcel: 12621034J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08229
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a COMcheck analysis of the building alterations. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope (i.e. window replacement) based on the current code. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Sections C101.4.3, C101.5, C103.2, and C303.1.3, IECC 2012.]
2. Correct the ventilation calculations and if you still need to increase the size of the A/C unit, provide heating/cooling load calculations and demonstrate compliance with the energy code using COMcheck. [Initial comment: If the exercise area in AC zone 3 is a change of use, provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.]
01/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/20/2015 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2015 AROMERO4 APPROVAL SHELF Completed
01/23/2015 AROMERO4 OUT TO CUSTOMER Completed
01/23/2015 AROMERO4 REJECT SHELF Completed