Permit Number: T14CM08199
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08199
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2015 STEVE SHIELDS ZONING REVIEW Approved
01/30/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/11/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved; sheets P-001, P-002, P-301, and P401 are not sealed. [Initial comment: Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.]
2. It is not clear that all of the plumbing fixtures needing to be directly-connected have been installed correctly: provide the equipment model numbers and specifications noted on sheet I-112 and a waste and vent diagram. [Initial comment: Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2012. Reference: Section 301.3, IPC 2012.
3. Comment not addressed. [Initial comment: The use of an island vent is restricted to sinks and lavatories (detail 05/P-401. Reference: Section 916.1, IPC 2012.
4. All vents shall be graded back to the drainage piping; see Section 905.2, IPC 2012. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
02/11/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.]