Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM08199
Parcel: 13355231A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08199
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2014 MARTIN BROWN FIRE REVIEW Approved
12/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-001; SITE INFORMATION/OCCUPANCY: THE OCCUPANT LOAD TABULATED ON A SQUARE FOOT BASIS IS LISTED AS 42. FOLLOWING THAT CALCULATION, A SEATING SUMMARY IS PROVIDED, LISTING 63 SEATS TOTAL AT THE INDOOR AND OUTDOOR SEATING AREAS. WHAT IS THE OCCUPANCY LOAD?
2. SHEET I-411: PROVIDE A TITLE AND AN ELEVATION NUMBER TO SEVERAL OF THE RESTROOM WALL ELEVATIONS.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/19/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
12/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2012. Reference: Section 301.3, IPC 2012.
3. Any fittings or connections in a drainage system that results in a reduction of the pipe area are prohibited (e.g. the 3" pipe downstream of the gravity grease interceptor). Reference: Section 706.2, IPC 2012.
4. The use of an island vent is restricted to sinks and lavatories (detail 05/P-401. Reference: Section 916.1, IPC 2012.
5. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
6. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. (A vent upstream of the gravity grease interceptor is not required.) Reference: Section 1003.9, IPC 2012.
12/19/2014 ROBERT SHERRY WATER REVIEW Completed
12/23/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/29/2014 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 9525 E. Old Spanish Trail, #113
T14CM08199
Building Plan (1st Review)

TRANSMITTAL DATE: December 29, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that out door seating is proposed. This out door seating is not shown on the last approved development plan. A revised development plan showing that vehicle parking requirements are met for the out door seating area and that pedestrian circulation is maintained must be provided prior to approval of this tenant improvement.

3. Zoning will approve the building plans once all other PDSD Agencies have approved.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2015 AROMERO4 APPROVAL SHELF Completed
01/27/2015 AROMERO4 OUT TO CUSTOMER Completed
01/27/2015 CPIERCE1 REJECT SHELF Completed