Permit Number: T14CM08192
Parcel: 10603087D

Address:
3200 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08192
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/26/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/29/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
02/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed; cleanouts for the canopy storm drains are shown on the civil plan C120 but they are not sufficient. [Initial comment: Provide a cleanout at the base of each vertical rainwater leader prior to connection to the horizontal storm drain below grade. Reference: Sections 708.3.4 and 1101.8, IPC 2012.]
2. Comment not addressed; the canopy storm drains are shown on the civil plan C120 and the pipe material shall be changed to comply with Section 1102.3, IPC 2012. Note that approved development plans are not to be used for construction of on-site utilities (e.g. water service to buildings, building sewer, building storm drains, site lighting, or electrical service to the buildings). The construction of the on-site utilities may be included with the permit for constructing the building. [Initial comment: The storm drain pipe proposed for use under the fuel canopy (PVC SDR 35) does not conform to one of the standards listed in Table 702.2, IPC 2012. Reference: Section 1102.3, IPC 2012.]