Permit Number: T14CM08192
Parcel: 10603087D

Address:
3200 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM08192
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2014 MARTIN BROWN FIRE REVIEW Approved Underground fuel tanks require separate, deferred submittal to the fire department.
12/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied
12/15/2014 JASON GREEN ENGINEERING REVIEW Approv-Cond Do not approve the building permit until both SEQ #'s are provided for the Covenants and the pedestrian access easement.
12/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the horizontal rainwater leader shown in detail H1/XC410 (Section at Canopy Sides); the notes in question say, "4" PVC coupler w/3" [diameter] field installed PVC in leader" and "4" PVC elbow w/ 3" [diameter] pipe". Reference: Section 1101.5, IPC 2012.
2. Provide a cleanout at the base of each vertical rainwater leader prior to connection to the horizontal storm drain below grade. Reference: Sections 708.3.4 and 1101.8, IPC 2012.
3. The storm drain pipe proposed for use under the fuel canopy (PVC SDR 35) does not conform to one of the standards listed in Table 702.2, IPC 2012. Reference: Section 1102.3, IPC 2012.
12/18/2014 ROBERT SHERRY WATER REVIEW Completed
12/23/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/23/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change See LHN condition by engineering for T14CM04541.
12/24/2014 FRODRIG2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2015 SHANAE POWELL REJECT SHELF Completed