Permit Number: T14CM08184
Parcel: 140260380

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08184
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2015 DAVID RIVERA ZONING REVIEW Reqs Change January 21, 2014

SEE COMMENTS UNDER T14CM07567
01/21/2015 JASON GREEN ENGINEERING REVIEW Reqs Change ENG will stamp the building plan approved upon approval of DP14-0189. JG
01/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/29/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
02/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/02/2015 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. Provide the location of the water meter and backflow preventer associated with the water meter serving this fuel station. Reference: Section 107.2.1, IBC 2012. Note: An approved development plan or an approved grading permit is not to be used for construction of on-site utilities (e.g. water service to buildings, building sewers, site lighting, or electrical service to buildings).
02/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The applicable standard is ASSE 1022, not ASSE 102.2. [Initial comment: At a minimum, beverage dispensers require the use of a backflow preventer that is listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012.]
2. Provide overflow protection for the canopy. [Initial comment: Provide roof drainage calculations and plans for the fuel canopy. Provide overflow protection for the canopy. Reference: Sections 1101, 1106 and 1108, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2015 SHANAE POWELL OUT TO CUSTOMER Completed
02/13/2015 CPIERCE1 REJECT SHELF Completed