Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T14CM08151
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Michael St.Paul, Planning Technician PROJECT: T14CM08151 2809 East Kaibab Vista Carport, bedroom & covered patio addition to SFR TRANSMITTAL: January 7, 2015 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The required setback to the north property line is six (6) feet. The proposed setback is three (3) feet. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). The minimum front setback is twenty (20) feet. The proposed setback for the patio along the front is fourteen (14) feet. The carport is proposed at eighteen (18) feet. |
| 01/07/2015 | MICHAEL ST. PAUL | NPPO | REVIEW | Passed | |
| 12/01/2014 | ANY | ENGINEERING | REVIEW | Active | |
| 12/01/2014 | ANY | BUILDING-RESIDENTIAL | REVIEW | Active |