Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T14CM08082
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/26/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 11/26/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 11/26/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/26/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/26/2014 | AROMERO4 | WWM | REVIEW | Completed | |
| 11/26/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/26/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/26/2014 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
| 11/26/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |