Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM08052
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please change design density on sheet P6 to Ordinary Group 2 (.20) for storage areas. Note 9 of Fire Sprinkler General Notes (sheet P6) incorrect. Golder Ranch is not the water purveyor for the project. Also, the fire sprinkler contractor shall perform a flow test to determine flow and pressure prior to installation of sprinkler system. |
| 12/02/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1; PROJECT DATA: THE 'CONSTRUCTION TYPE' INDICATES VB, UN-SPRINKLERED AT WAREHOUSE AND SPRINKLERED AT RESIDENCE, WHILE THE 'SPRINKLER SYSTEM' INDICATES FULL AUTOMATIC SPRINKLER SYSTEM AT RESIDENCE AND AT WAREHOUSE. COORDINATE PER THE IBC SECTION 903. 2. SHEET G1; PROJECT DATA: THE 'POSTED OCCUPANCY' INDICATES ONE EXIT REQUIRED FOR LESS THAN 49 OCCUPANTS PER THE IMC TABLE 403.3. THE IBC TABLE 1015.1 INDICATES A MAXIMUM OF TEN OCCUPANTS FOR ONE EXIT IN THE R OCCUPANCY, AND 29 OCCUPANTS FOR ONE EXIT IN THE S OCCUPANCY. CLARIFY. 3. SHEET G1; DEFERRED ITEMS: IT IS INDICATED IN THE PROJECT DATA THIS PROJECT WILL HAVE A FIRE ALARM SYSTEM. ADD THAT TO THE 'DEFERRED ITEMS' NOTE. 4. SHEET G1; PROJECT DATA: THE 'ACCESS AND EXIT FACILITIES' REFERENCES THE 2006 IBC AND SECTIONS 1004 AND 1005. REVISE THE IBC EDITION AND REVISE 'ACCESS' TO 'EGRESS'. 5. SHEET G1; PROJECT DATA: THE 'EXITS WIDTH' REFERENCES THE IBC SECTION 1004.3.2.2. REVISE THE SECTION REFERENCE. 6. SHEET G1; PROJECT DATA: THE 'BUILDING CODES' REFERENCES THE 2009 NEC. REVISE TO THE 2011 EDITION. 7. GENERAL: PER THE IBC TABLE 508.4, THE R-3 AND S-2 OCCUPANCIES MUST BE SEPARATED BY A ONE OR TWO HOUR FIRE ASSEMBLY. ADDRESS THIS IN YOUR PROJECT DATA AND PROVIDE DETAILS ON THE DRAWINGS, INCLUDING SPRINKLER SYSTEMS REQUIRED. 8. SHEET S1; FOUNDATION PLAN: FINISH THE SECTION CUT ON THE PLAN NEAR THE RESTROOMS. 9. SHEET S1; FOUNDATION PLAN KEYNOTES: NOTES 31 AND 32 WERE NOT LOCATED ON THE PLAN. REFERENCE SHEET S1.1. 10. SHEET S1.1; FOUNDATION PLAN KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE PLAN. REFERENCE SHEET S1. 11. SHEET S2 (STEEL LINTEL SCHEDULE); STRUCTURAL CALCULATIONS: THE LINTELS L-2, L-3, AND L-4 WERE NOT LOCATED IN THE CALCULATIONS. VERIFY AND PROVIDE. 12. SHEET S2; HEADER SCHEDULE: ARE THERE ANY WOOD HEADERS IN THIS SCHEDULE INDICATED ON THE PLANS? VERIFY AND REMOVE AS REQUIRED. 13. SHEET S2; FRAMING PLAN KEYNOTES: NOTE 3 INDICATES IT IS 'NOT USED', BUT SHOWS UP IN THE NORTHEAST PORTION OF THE PLAN. CLARIFY. 14. SHEETS S2 AND S2.1; FRAMING PLAN KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE PLANS. VERIFY AND/OR REFERENCE OTHER SHEETS. 15. SHEET S2.1; FIRE STOPS ELEVATION: REFERENCE IS MADE TO THE IRC FOR FIRE STOPS. THE FIRE SEPARATION BETWEEN THE RESIDENTIAL AND COMMERCIAL PORTIONS MUST MEET THE 2012 IBC REQUIREMENTS. REVISE. 16. SHEET A1; FLOOR PLAN KEYNOTES: NOTES 13, 24, 26, 28, 29, AND 30 WERE NOT LOCATED ON THE PLAN. VERIFY AND/OR REFERENCE OTHER SHEETS. 17. SHEET A1 (KEYNOTE 15); SHEET A2 (FLOOR PLAN KEYNOTE 8): NOTE 15 INDICATES A 6" SQUARE TUBE STEEL COLUMN, WHILE NOTE 8 INDICATES A 4" SQUARE TUBE STEEL COLUMN. COORDINATE. THE STAIR MANUFACTURER WILL DETERMINE THAT COLUMN SIZE. 18. SHEETS A1.1 AND A1.2; FLOOR PLAN KEYNOTES: NOTES 13, 24, 26, 28, 29, AND 30 WERE NOT LOCATED ON THE PLAN. VERIFY AND/OR REFERENCE OTHER SHEETS. 19. SHEET A2; HANDICAP ACCESSIBLE KEYNOTES: NOTE 11 REFERENCES ANSI 4.27.4 FOR HANDICAP FAUCETS. REVISE THE SECTION REFERENCE NUMBER. 20. SHEET A2; HANDICAP ACCESSIBLE KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE ELEVATIONS. VERIFY. 21. SHEET A2 (FLOOR PLAN); SHEET A10 (SECTION 8); SHEET S2.1 (FLOOR FRAMING PLAN): SECTION 8/A10 INDICATES A DOUBLE ANGLE LINTEL (AT TWO LOCATIONS), WHILE THE STRUCTURAL PLAN INDICATES A 12" STEEL BEAM. COORDINATE. 22. SHEET A3; FLOOR PLAN KEYNOTES: NOTES 7, 8, 10, AND 29 WERE NOT LOCATED ON THE PLAN. VERIFY. 23. SHEET A5; ELEVATION KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE ELEVATIONS. VERIFY. 24. SHEET A6; ROOF PLAN KEYNOTES: NOTES 12, 17, AND 25 WERE NOT LOCATED ON THE PLAN. VERIFY. 25. SHEETS A7 AND A7.1; SECTION KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE SECTIONS. VERIFY AND/OR REFERENCE OTHER SHEETS. 26. SHEETS A8, A8.1, A8.2, AND A8.3; ELEVATION KEYNOTES: NOTES 45 AND 46 WERE NOT LOCATED ON THE ELEVATIONS. VERIFY. 27. SHEET A8.2; NORTH ELEVATION: FINISH THE KEYNOTE INDICATED ON THE LEFT END OF THE ELEVATION. 28. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/16/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the size of the waste stack located at the south end of the building; it is 3" on the second floor but 4" on the first floor. 2. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Provide overflow protection for the roof. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012. |
| 12/16/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 3. Show how the "Additional Efficiency Package Requirements" noted in Section C406, IECC 2012 is to be addressed (commercial areas only). Reference: Section C401.2.1, IECC 2012. 4. Show the size, routing, and termination of the condensate drain for the split system heat pump. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 5. Provide information to show that the termination of the restroom exhaust complies with the requirements of Sections 501.3.1 (3) and 501.3.1.1, IMC 2012. |
| 12/16/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/19/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM08052 1. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, NEC 210.12. 2. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, NEC 406.12. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
| 12/22/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | Approval of DP14-0216 required. Building plans must match the final approval plans for the development package. |
| 12/22/2014 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Reqs Change | Bldg plan can not be approved due to substantial remaining items, including TSMR, on Development Package DP14-0216. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/05/2015 | CPIERCE1 | REJECT SHELF | Completed |