| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that the control system provides for automatic start of the roof top units (Section C403.2.4.3.3, IECC 2012). [Initial comment: Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. (Would this be on sheet CRT-1, which was not included in the submitted drawing package?) Reference: Section C303.1, International Energy Conservation Code 2012.] |
| 01/02/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A tempering valve rated per ASSE 1069 may not be used as a substitute for an ASSE-listed mixing valve. [Initial comment: The specified "tempering valve", Watts model N170L, is an obsolete product that is no longer listed. Provide an alternative device. Reference: Section 303.4, IPC 2012.] 2. Comment not addressed. [Initial comment: Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.] 3. One floor sink has a flat vent. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |
| 01/06/2015 | FRODRIG2 | ZONING | REVIEW | Needs Review | |
| 01/06/2015 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |