Permit Number: T14CM08010
Parcel: 13321075A

Address:
10 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08010
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the control system provides for automatic start of the roof top units (Section C403.2.4.3.3, IECC 2012). [Initial comment: Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. (Would this be on sheet CRT-1, which was not included in the submitted drawing package?) Reference: Section C303.1, International Energy Conservation Code 2012.]
01/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. A tempering valve rated per ASSE 1069 may not be used as a substitute for an ASSE-listed mixing valve. [Initial comment: The specified "tempering valve", Watts model N170L, is an obsolete product that is no longer listed. Provide an alternative device. Reference: Section 303.4, IPC 2012.]
2. Comment not addressed. [Initial comment: Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.]
3. One floor sink has a flat vent. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.]
01/06/2015 FRODRIG2 ZONING REVIEW Needs Review
01/06/2015 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review