Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM08010
Parcel: 13321075A

Address:
10 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM08010
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2014 KEN BROUILLETTE FIRE REVIEW Approved
11/28/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-1 (FLOOR PLAN); SHEET A-3 (BUILDING SECTION 2): SECTION 2/A-3 IS CUT THROUGH AN AWNING (ON THE NORTH WALL), BUT THAT AWNING DOES NOT SHOW UP ON THE SECTION. CLARIFY.
2. SHEET A-1 (FLOOR PLAN); SHEET A-6 (WALL SECTION 1): SECTION 1/A-6 SHOULD INDICATE THE AWNING IS 'BEYOND'.
3. SHEET A-1 (FLOOR PLAN); SHEET A-8 (SECTION 2): SECTION 2/A-8 CUT THROUGH THE SOUTH WALL SHOULD BE NOTED AS 'SIMILAR' (ROOF TRUSSES BEAR ON THIS WALL).
4. SHEET A-1; FLOOR PLAN: AT THE SOUTHWEST CORNER OF THE BUILDING, KEYNOTE 2 REFERENCES A STEEL GUARD POST. PROVIDE A DETAIL OR DETAIL REFERENCE FOR THAT POST.
5. SHEET A-1; KEYNOTES: NOTE 15 REFERENCES J/A-9 FOR A WINDOW DETAIL. THAT DETAIL WAS NOT LOCATED ON SHEET A-9. CLARIFY.
6. SHEET A-2: ADD A REFERENCE ON THIS SHEET TO SHEET A-2.1 FOR EXTERIOR MATERIALS AND FINISH SCHEDULE.
7. SHEET A-3.1; RESTROOM/KITCHEN ACCESSORIES: NOTES G, H, AND I WERE NOT LOCATED ON THE PLANS OR ELEVATIONS. VERIFY.
8. SHEET A-4; KEYED NOTES: NOTES 2, 4, AND 7 WERE NOT LOCATED ON THE PLAN. VERIFY.
9. SHEET A-4; ROOF PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN DIMENSIONS.
10. SHEET A-5; REFLECTED CEILING PLAN: ADD KEYNOTE 3 TO THE AWNING IN THE NORTHEAST CORNER (EAST WALL) OF THE BUILDING.
11. SHEET A-5; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE PLAN. VERIFY.
12. SHEET A-6 (SECTION 3); SHEET A-8 (SECTION 2): IDENTIFY THE AWNING IN BOTH SECTIONS.
13. SHEET A-6; WALL SECTION 1: THE DETAIL J/A-9 (AT THE STOREFRONT SILL) IS NOT INDICATED ON SHEET A-9. VERIFY.
14. SHEET A-9; DETAILS A THROUGH L: REVISE THE TITLE REFERENCE LETTERS (A, B, C...ETC).
15. SHEET S-1; STRUCTURAL NOTES (FOUNDATIONS): THE FIRST THREE NOTES INDICATE A GEOTECHNICAL REPORT WAS USED IN THE FOUNDATION DESIGN. PROVIDE THAT REPORT FOR REVIEW.
16. GENERAL: THE IBC SECTION 1109.11 INDICATES AN ACCESSIBLE SEATING REQUIREMENT. SHOW ON A PLAN THE LOCATION OF THE ACCESSIBLE SEATING IN THE DINING ROOM.
17. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/02/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/05/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Burger King - 10 N. Wilmot Road
T14CM08010
Building Plan (1st Review)

TRANSMITTAL DATE: December 5, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans and they appear to in compliance with the approved development package, but until the development package is fully approved by all PDSD review agencies Zoning cannot approve the building plans.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Once all other PDSD review agencies have approved the plans Zoning will approve. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/05/2014 JASON GREEN ENGINEERING REVIEW Approved
12/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the building components used in the energy code analysis for the building envelope with those shown on the drawing. The roof insulation is shown as R-33 in the analysis and in the sections on sheet A6 but is labeled as R-30 on sheet A7. In addition, the continuous insulation noted as R-0.8 on the energy code analysis is not identified in any of the sections. Reference: Section C303.1, IECC 2012, as amended by the City of Tucson.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. (NFRC certification numbers can be found at www.nfrc.org) Reference: Section C303.1.3, IECC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
4. Show that the proposed rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
5. Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. (Would this be on sheet CRT-1, which was not included in the submitted drawing package?) Reference: Section C303.1, International Energy Conservation Code 2012.
6. Verify the sequence of operation for the restroom exhaust fan will ensure that all of the air supplied to the restrooms will be exhausted during the occupied hours for the building. Reference: Section 403.2.1 (4), IMC 2012.
7. Verify that the distribution of supply air from the HVAC units during the heating season complies with the requirements of footnote (g) of Table 403.3.1.2, IMC 2012 or use a zone air distribution effectiveness value of 0.8 for the ventilation calculations. Reference: Section 403.3.1.2, IMC 2012.
8. Verify that the proposed Type I hoods are equipped to automatically start the hood exhaust fans when cooking operations commence. Reference: Section 507.2.1.1, IMC 2012.
12/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 104.2 and 107.2.1, IBC 2012.
2. The note on the water and gas plan calls for a maximum gas pressure of 10" WG into the building. Verify minimum gas pressures required for the cooking appliances as Southwest Gas generally will provide service only at 7"WC, 2 PSIG, or 5PSIG.
3. Verify the gas input for the rooftop units and the fryers: the mechanical schedule and the kitchen equipment schedule have different input values. Reference: Section 107.2.1, IBC 2012.
4. Revise the water riser diagram to include the hot water return piping. Reference: Section 107.2.1, IBC 2012.
5. The specified "tempering valve", Watts model N170L, is an obsolete product that is no longer listed. Provide an alternative device. Reference: Section 303.4, IPC 2012.
6. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
7. Verify that the pipe sizes called out for the water closet flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012.
8. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. (See also, general note 10 on sheet P-2 which conflicts with the note requiring double check valves at directly-connected appliances.) Reference: Section 608.16.1, IPC 2012.
9. Clarify general note 12 on sheet P-2: where is the can wash and where is the trash enclosure? Reference: Section 107.2.1, IBC 2012.
10. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
11. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
12. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
13. Provide sizing calculations for the gravity grease interceptor using the calculation method shown in Section 1003.3, IPC 2012, as amended by the City of Tucson.
12/15/2014 ROBERT SHERRY WATER REVIEW Completed
12/17/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM08010

1. Clarify the location of keynote #2 on the Electrical site plan sheet #E.0.

2. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: Compare total fixture output to the budget based on property size and zone location (Table 401.1).
Include all exterior (existing) fixtures within the property lines or business allocation. The ordinance requires identification of each fixture type (both Full-Cut-Off and un-shielded); and fixture output based on a typical lamp lumen output at the maximum fixture wattage rating.

The 2012 Outdoor Lighting Code may be found on The City of Tucson Website under: www.tucsonaz.gov/pdsd; Codes, Standards, Ordinances & Guidelines; Building Codes.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4912
Kenneth.VanKarsen@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2014 FERNE RODRIGUEZ APPROVAL SHELF Completed
12/19/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/19/2014 CPIERCE1 REJECT SHELF Completed