Permit Number: T14CM07939
Parcel: 13507461C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07939
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2014 MARTIN BROWN FIRE REVIEW Approved
12/10/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change COVER SHEET
1. At the Code Analsis Summary please include the total occupancy load of 280 occupants.
SHEET A1.1
2. Provide a complete Occupancy Load summary including total.
SHEET A2.0
3. Provide water dispensers as per the 2012 IBC, Section 1109.5 and the 2009 ICC A117.1, Section 602. Bottled water dispensers do not meet the code requirement.
SHEET A4.0
4. At detail 1, Men's toilet room shower, provide inside clearances as required by the 2009 ICC A117.1, Section 404.2.3 (e).
END OF REVIEW
12/22/2014 ROBERT SHERRY WATER REVIEW Completed
12/22/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the component description for the new fenestration in the Envelope Compliance Certificate to either include the NFRC fenestration product ratings for the Solar Heat Gain Coefficient (SHGC) or U-factor or use the appropriate default SHGC and default U-factor from Tables C303.1.3 (1), C303.1.3 (2), and C303.1.3 (3), IECC 2012. (See www.nfrc.org for the Certified Product Description number, CPD#) Reference: Section C303.1.3, IEC 2012.
2. The Envelope Compliance Certificate indicates that the roof has been modified to include cavity insulation with an R-value of R-38. Where is this covered in the drawing set?
3. Keynote 9 on sheet A2.0 indicates that ten microwave ovens will be installed in the break room. Provide general room exhaust for the cooking appliances with a minimum exhaust rate shall of 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
4. Heat pump HP-14 is listed twice in the ventilation calculations; should one of the entries be for HP-16?
12/30/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed