Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM07871
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2014 MARTIN BROWN FIRE REVIEW Approved
11/28/2014 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: David Rivera
Principal Planner

PROJECT: DP14-0211
3420 N. Craycroft Road
Development Package - Site Grading Erosion Protection Plan

TRANSMITTAL DATE: November 28, 2014

DUE DATE: December 17, 2014

COMMENTS: Zoning conditionally approves the Erosion Protection Walls Permit pending approval of the Development Package.If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
12/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S2 (SECTION A); GEOTECHNICAL EVALUATION (PAGE 24); STRUCTURAL CALCULATIONS (PAGE 2): THE GEOTECHNICAL EVALUATION AND THE STRUCTURAL CALCULATIONS INDICATE WALL SECTION A HAS 19' OF FREEBOARD AND 16' OF WALL EMBEDMENT, WHILE SECTION A/S2 INDICATES 16' OF FREEBOARD AND 16' OF WALL EMBEDMENT. CLARIFY.
2. SHEET S2 (SECTION C); GEOTECHNICAL EVALUATION (PAGE 24); STRUCTURAL CALCULATIONS (PAGE 2): THE GEOTECHNICAL EVALUATION AND THE STRUCTURAL CALCULATIONS INDICATE WALL SECTION C/S2 HAS 18' OF FREEBOARD AND 12' OF WALL EMBEDMENT, WHILE SECTION C/S2 INDICATES 15' OR 16' OF FREEBOARD AND 12' OF WALL EMBEDMENT. CLARIFY.
3. SHEET S2; SECTION C: THE WEST FREEBOARD DIMENSION INDICATES 115'-0". REVISE.
4. SHEET S2; WALL SECTION C: THE SECTION INDICATES TWO DIFFERENT WALL HEIGHTS (27'-0" AND 28'-0"). INDICATE ON THE WALL PLAN ON SHEET S1 WHERE THAT TRANSITION OCCURS.
5. SHEET S3 (SECTION E); GEOTECHNICAL EVALUATION (PAGE 24); STRUCTURAL CALCULATIONS (PAGE 2): THE GEOTECHNICAL EVALUATION AND THE STRUCTURAL CALCULATIONS INDICATE WALL SECTION E HAS 14' OF FREEBOARD AND 14' OF WALL EMBEDMENT, WHILE SECTION E/S3 INDICATES 13' OF FREEBOARD AND 14' OF WALL EMBEDMENT. CLARIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/17/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change permit may not be issued until floodplain use permit is approved/issued.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2014 AROMERO4 OUT TO CUSTOMER Completed