07/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE PROVIDE ELECTRICAL WIRING METHODS ON THE ELECTRICAL PLANS AS REQUIRED FOR ALL THE GAS FIRED EQUIPMENT, HEATERS, KITCHEN EQUIPMENT SHOWN ON THE PLAN SHEET 3P1.1.
REF; 2012 IBC 107.2.1, 2011 NEC
07/27/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a "NON-POTABLE" label for the post-hydrants. [Initial comment: Stop-and-waste valves (e.g. the proposed post-hydrants for the baptistery) are prohibited per Section 608.7, IPC 2012 unless the potable water upstream of the hydrant is protected by an approved backflow preventer and the water from the hydrant is labeled as "non-potable".]
Comment not addressed. [Initial comment: Clarify the intended purpose of the gas outlets with the quick-disconnects and their actual location (they are not shown on the architectural plans). Reference: Section 107.2.1, IBC 2012.]
07/27/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Details not provided. [Initial comment: Provide details showing how the infrared heaters are mounted and what the clearances are to the structure and to the area below the heater.]