Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM07870
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. It appears the Baptismal is only shown on the site plan OE1.O and there several devices, lighting fixtures, clustered in one location. Please provide a larger detail showing all the equipment locations in detail. Verify feeder conduit, conductor sizes and types, OCPD, and circuiting of the RV Pedistal shown on the panel schedule for panel 3A. Ref: IBC 107.2.1 |
| 04/04/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide details showing how the infrared heaters are mounted and what the clearances are to the structure and to the area below the heater. |
| 04/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Stop-and-waste valves (e.g. the proposed post-hydrants for the baptistery) are prohibited per Section 608.7, IPC 2012 unless the potable water upstream of the hydrant is protected by an approved backflow preventer and the water from the hydrant is labeled as "non-potable". 2. Clarify the intended purpose of the gas outlets with the quick-disconnects and their actual location (they are not shown on the architectural plans). Reference: Section 107.2.1, IBC 2012. |
| 04/05/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |