Permit Number: T14CM07870
Parcel: 14102013D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM07870
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change PREVIOUS COMMENT 9
SHEET 3a1.0
1. Provide a large scale detail of the new ramp showing all accessible requirements including grade differences, dimensioning, slope, handrails in plan and elevation and landings.
a. Reference the large scale detail from detail 1/3a1.0.
PREVIOUS COMMENT 13
SHEET 3a6.0
2. Note 7.15 is pointing at the new steel bond beam which references the roof system. Provide another note referencing the steel bond beam to detail 3/a9.3.
a. At details 1 and 2/3a6.1, shouldn't the bond beam be shown on these two building sections?
PREVIOUIS COMMENT 16
3. In the structural engineer's separate letter, he indicates the certification is attached to this submittal. It is not to be found.
END OF REVIEW
11/24/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Final approval of DP14-0177 is required.
11/24/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/25/2014 KEN BROUILLETTE FIRE REVIEW Approved
11/26/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved Engineering will stamp plan once all comments have been addressed for all reviewers.
12/01/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07870

1. Provide any proposed electrical or lighting associated with the baptismal structures.
2. Clarify fixture type A on sheet 0e.1.0. The plan shows seven (one near future building 1) although the lumen calc shows four.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
12/09/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plumbing plans to show how the baptismal will be filled and how (and to where) it will be drained. Reference: Section 107.2.1, IBC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2014 CPIERCE1 REJECT SHELF Completed