Permit Number: T14CM07810
Parcel: 112061730

Address:
2614 N NORTON AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM07810
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-12-14
Activity: T14CM07810
Address: 2614 N. Norton Ave
Applicant: Philip Veneziano

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

MECHANICAL PLAN:
1. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

OUTDOOR LIGHTING CODE
2. Exterior flood lighting must be classified and calculated as unshielded lighting on OLC calculation.
3. Exterior lighting within 25 feet of adjacent residential property lines must be fully shielded, 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:
4. Specify the insulation material that will provide a rating of R-38 in a 7.25" cavity as indicated.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2014 SHANAE POWELL REJECT SHELF Completed