Permit Number: T14CM07647
Parcel: 11714407B

Address:
560 S CONVENT AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T14CM07647
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2014 STEVE SHIELDS ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT:
T14CM07647
576 S. Convent Ave.
Remodel Existing Dwelling and Guest House

TRANSMITTAL: November 12, 2014

COMMENTS: the following comments are relative to an application for Historic Review and Design Development Option (DDO) (UDC 3.11.1).

Historic Review required for façade changes to the residence.

DDO required for perimeter yard setback to the northwest property line.

This site is located in the HO-3 zone (UDC 4.7.15). A single-family residence (SFR) with 2nd Unit is a permitted use in this zone (Table 4.8-3).

The minimum setback is the greater of ten (10) feet, or three-fourth (3/4) the height of the structure's wall facing each interior property line (Table 6.3-3.A). Existing setback is 0'-4".

Until the above comments have been addressed Zoning cannot approve the building plans. Ensure that Historic Review has approved and stamped prior to the next submittal.
12/10/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-10-14
Activity: T14CM07647
Address: 576 S. Convent
Applicant: Kegan Tom

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Show the waste cleanouts within 2' from the building on the building drain, P3005.2.
2. Show gray water diverter valve on gray water line and connecting downstream of the backwater valve.
3. Kitchen sink waste is not considered gray water. Clarify notation.

ELECTRICAL PLAN:
4. The small appliance receptacles serving kitchen counters must be divided between (2) 20 amp circuits, E3901.3.
5. The dedicated bathroom circuits may not share outlets located in other rooms, E3703.4, E3901.6.
6. Electrical panels may not be located in a closet, E3405.4.
7. Provide receptacles spaced according to E3901.2 in study 1W.

OUTDOOR LIGHTING CODE
8. Exterior lighting within 25 feet of adjacent residential property lines must be fully shielded, 401.3.3.
9. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.
10. Provide consistent information between sheets E0.1 and E1.0 regarding the location and quantity of exterior lighting.
11. Clarify motion sensor lighting. Two bulbs at 200 watts does not equal 1000 lumens per fixture.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2014 AROMERO4 REJECT SHELF Completed