Permit Number: T14CM07625
Parcel: 141314410

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T14CM07625
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM07625

PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
DIAGRAMS / CALCULATIONS
1. Provide a cross-sectional area calculation showing 40 percent fill compliance, NEC 358.22. The PV conductors may overfill a ¾" conduit capacity.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2015 SHANAE POWELL APPROVAL SHELF Completed
01/23/2015 SHANAE POWELL OUT TO CUSTOMER Completed