Permit Number: T14CM07612
Parcel: 13214078M

Address:
3737 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM07612
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The contributory area of the breezeway roof drains only onto the eastern portion of the office roof; based on the locations of the crickets, each scupper drains only a specific portion of the roof structure. Hydraulic sizing of the scuppers is not the same as using Table 1106.2 (1), IPC 2012 to determine the size of a downspout. Details 1a/A2 and 2/A2 appear to have conflicting dimensions; clarify where each is used. [Initial comment: Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Include the effect of any vertical walls that can divert rainfall onto the roof. Show all dimensions for the roof scuppers and the downspouts. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.]
2. Each overflow scupper drains only a specific portion of the roof structure due to the presence of crickets. Clarify how the overflow scuppers protect each roof area. [Initial comment: Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2015 SHANAE POWELL OUT TO CUSTOMER Completed
04/14/2015 CPIERCE1 REJECT SHELF Completed