Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM07612
Parcel: 13214078M

Address:
3737 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM07612
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A2
1. Please define the existing roof decks and membraine systems used on all buildings and covered breezeways.
a. For all metal roof systems please provide flashing details at parapet wall abuttments and valley edges of new crickets and etc.
2. Are you really draining the east side of the office buildng on the mechanical units? Reference mechanical/plumbing comments.
CALCULATIONS
3. Provide an utlimate wind design load of 115 mpg.
END OF REVIEW
12/05/2014 KEN BROUILLETTE FIRE REVIEW Completed
12/11/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify how the rainwater from the roof areas will be directed away from the buildings. Reference: Section 1101.2, IPC 2012.
2. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Include the effect of any vertical walls that can divert rainfall onto the roof. Show all dimensions for the roof scuppers and the downspouts. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.
3. Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2014 FERNE RODRIGUEZ APPROVAL SHELF Completed
12/15/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/15/2014 CPIERCE1 REJECT SHELF Completed