Permit Number: T14CM07592
Parcel: 127081910

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07592
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
12/03/2014 LOREN MAKUS ENGINEERING REVIEW Approved
12/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/03/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/04/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Show how the "Additional Efficiency Package Requirements" noted in Section C406, IECC 2012 is to be addressed. Reference: Section C401.2.1, IECC 2012.Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the Solar Heat Gain Coefficient (SHGC) on COMcheck or use the appropriate default SHGC from Table C303.1.3 (2), IECC 2012. Coordinate the SHGC values shown on the COMcheck Envelope Compliance Certificate with the window descriptions shown on the drawings. Reference: Section C303.1.3, IEC 2012.
3. Show that the proposed replacement rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
12/04/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07592

1. Lighting fixture information: provide an updated Interior Lighting Compliance Certificate with consistent fixture types and wattage as shown on the Light Fixture Schedule, C405.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
12/04/2014 ROBERT SHERRY WATER REVIEW Reqs Change Verify that an approved reduced pressure backflow prevention assembly will be installed at the water meter.
12/04/2014 MARTIN BROWN FIRE REVIEW Approved
12/04/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/16/2014 SPOWELL1 WWM REVIEW Needs Review