Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. D7, D8, D9, D10 (3 units), D15, D16, and D17). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
2. Provide listing information to show that the dishwasher, S-6, does not require the installation of a Type II hood. Reference: Section 507.2.2, IMC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
4. Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
12/05/2014 ROBERT SHERRY WATER REVIEW Reqs Change Show the size and location of the water meter and the reduced pressure backflow preventer serving this restaurant. State the total demand served by the water meter.
12/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.