Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM07567
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/21/2015 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | PROJECT: T14CM07567 Walmart Neighborhood Store Building Plan Review TRANSMITTAL DATE: January 21, 2015 DUE DATE: February 13, 2015 COMMENTS: 01. Zoning has reviewed the building plans as it pertains to the zoning review purview. While the building plans are in substantial compliance with the preliminary development plans under current review, zoning cannot approve the building plans until the DP is fully approved and all building discipline reviewers have approved the building plans. 02. Zoning will do a follow up review of the building plans on the next submittal and do a comparison of the building plans to the DP once again to ensure consistency as it pertains to the zoning review purview of the building plans. 03. The Development package has not been approved as of this building review. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. |
01/21/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | ENG will stamp the building plan approved upon approval of DP14-0189. JG |
01/27/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 7: THE DATE THAT THE REGISTERED ARCHITECT SEALED THE SUBMITTAL DRAWINGS WAS NOT ADDED PER THE IBC SECTION 107 AND THE ARIZONA STATE BOARD OF PROFESSIONAL REGISTRATION. DATE ALL APPLICABLE DRAWINGS. |
01/30/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/30/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The minimum font size is 3/32"; also, provide the size of the water meter. [Initial comment: Provide the water demand calculation for the building along with the size of the proposed water meter.] |
01/30/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/13/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
02/13/2015 | CPIERCE1 | REJECT SHELF | Completed |