Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM07567
Parcel: 140260380

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM07567
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2014 JASON GREEN ENGINEERING REVIEW Reqs Change ENG will stamp the building plan approved upon approval of DP14-0189. JG
11/13/2014 KEN BROUILLETTE FIRE REVIEW Approved
11/17/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN: INDICATE THE ENLARGED WALK-IN PLANS (4/A5) ON SHEET A1.
2. SHEET S2 (DETAIL 5); STRUCTURAL CALCULATIONS (PAGE 78): THE CALCULATIONS INDICATE THE RETAINING WALL AT THE DOCK IS 12" THICK, WHILE THE DETAIL INDICATES 10". CLARIFY.
3. SHEET S4 (SPREAD FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (PAGE 71): COLUMN FOOTINGS 1-B (F2), 1-C (F2), 2-B (F1), 2-C (F1), 3-B (F1), 3-C (F1), 5-B (F1), 5-C (F1), 5-D.1 (F3), 6-B (F2A), AND 6-C (F2A) INDICATE A 1'-3" THICKNESS IN THE FOOTING SCHEDULE, BUT A 1'-6" THICKNESS IN THE CALCULATIONS. CLARIFY.
4. SHEET S4 (SPREAD FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (PAGE 71): COLUMN FOOTING 4-B (F1) INDICATES A 7'-0" X 7'-0 X 1'-3" FOOTING IN THE SCHEDULE, BUT A 8'-0" X 8'-0" X 1'-6" FOOTING IN THE CALCULATIONS. CLARIFY.
5. SHEET S4 (SPREAD FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (PAGE 71): COLUMN FOOTING 4.2-D.1 (F1) INDICATES A 7'-0" X 7'-0" X 1'-3" FOOTING IN THE SCHEDULE, BUT A 5'-0" X 5'-0" X 1'-6" FOOTING IN THE CALCULATIONS. CLARIFY.
6. STRUCTURAL CALCULATIONS; PAGE 2 (WIND LOADS): THE WIND SPEED INDICATES 90 MPH (ULTIMATE). THE CALCULATIONS ON PAGE 5 DO INDICATE A 115 MPH ULTIMATE WIND SPEED, SO CHANGE PAGE 2 TO COORDINATE.
7. GENERAL: THE DATE THAT THE REGISTERED ARCHITECT SEALED THE SUBMITTAL DRAWINGS IS MISSING. PROVIDE.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/18/2014 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T14CM07567
Walmart Neighborhood Store
Building Plan Review

TRANSMITTAL DATE: November 18, 2014

DUE DATE: December 4, 2014

COMMENTS:

01. Zoning has reviewed the building plans as it pertains to the zoning review purview. While the building plans are in substantial compliance with the preliminary development plans under current review, zoning cannot approve the building plans until the DP is fully approved and all building discipline reviewers have approved the building plans.

02. Zoning will do a follow up review of the building plans on the next submittal and do a comparison of the building plans to the DP once again to ensure consistency as it pertains to the zoning review purview of the building plans.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
11/19/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/04/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide separate indirect waste pipes for each compartment of the 3-compartment sinks to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
2. Clarify the entries in the size column of the gas pipe sizing calculations (i.e. if these are the actual pipe sizes, why don't they match the pipe sizes shown on the HVAC pan 1/M1?).
12/05/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07567

1. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: Compare total fixture output to the budget based on property size and zone location (Table 401.1).
a. The rated color temperature of proposed fixtures shall not exceed 3500K, Section 402. Notate plans, or provide manufacturer spec sheet with color temperature rating.
b. Update the Exterior Lighting times shown on sheet EM2 in conformance with the 2012 Outdoor Lighting Code Table 501.5. The curfew time is 12:00 A.M. unless business activities continue after this time. If appropriate, state the closing time at a footnote.

The 2012 Outdoor Lighting Code may be found on The City of Tucson Website under: www.tucsonaz.gov/pdsd; Codes, Standards, Ordinances & Guidelines; Building Codes.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
12/05/2014 ROBERT SHERRY WATER REVIEW Reqs Change Provide the water demand calculation for the building along with the size of the proposed water meter.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2015 AROMERO4 OUT TO CUSTOMER Completed