Review Details: REVISION - - 1ST

Permit Number - T14CM07531
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2015 DAVID RIVERA ZONING REVIEW Needs Review
07/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the dimensions of the roof scupper and downspout for the new pump house. Reference: Sections 1106 and 1108.3, IPC 2012.
2. Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
07/24/2015 KEN BROUILLETTE FIRE REVIEW Approved
07/24/2015 LOREN MAKUS ENGINEERING REVIEW Approved
07/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/27/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed