Permit Number: T14CM07531
Parcel: 141186350

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM07531
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/02/2015 DAVID RIVERA ZONING REVIEW Approved
02/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the calculations used to determine the water demand for the building; using Tables E103.3 (2) and E103.3 (3), IPC 2012 for public fixtures in a predominately flush-valve system, the demand is approximately 80 GPM, not 40 GPM. Reference: Section 604.1, IPC 2012. [Initial comment: Verify that the water velocity in the proposed 2" water service pipe will not exceed the maximum velocity recommended by the manufacturer (i.e. 8 FPS). Reference: Section 303.2, IPC 2012.]
2. Specify ASSE 1070-listed mixing valves for the lavatories in the restrooms. [Initial comment: Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.]
3. Coffee makers and other beverage dispensers require the use of backflow preventers listed to ASSE 1022; the proposed dual check valve (the LF7RU-U2 is not a vacuum breaker) is listed to ASSE 1024. Reference: Section 608.16.10, IPC 2012. [Initial comment: The Watts model Cu7 double check valve is an obsolete product and does not have an ASSE listing. Provide a backflow protection device that is listed for the intended application. Reference: Sections 608.1 and 608.16.10, IPC 2012.]
4. The next upstream manhole is shown on sheet C701 and appears to have a rim elevation of about 3019'. Verify the rim elevation with the civil engineers and determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.]
02/06/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
02/24/2015 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2015 SHANAE POWELL OUT TO CUSTOMER Completed
02/25/2015 CPIERCE1 REJECT SHELF Completed