Permit Number: T14CM07531
Parcel: 141186350

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM07531
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2014 KEN BROUILLETTE FIRE REVIEW Approved
12/01/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET G300
1. Why is exiting not shown going out the front entrance door?
STRUCTURAL
2. Need certification of special inspectors. The two part form is available on our web site.
3. Provide structural calcualations and details for the followings:
a. All roof top mounted HVAC equipment
b. All suspended medical equipment
c. Rack mounted water heaters
d. deconamination tank foundation
e. Exterior light pole foundations
END OF REVIEW
12/01/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/04/2014 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T14CM07531
10146 E. Old Vail Road
Medical Outpatient Facility

TRANSMITTAL DATE: December 4, 2014

DUE DATE: December 22, 2014

COMMENTS:

01. Zoning has reviewed the building plans for compliance with the revised and approved DP/TP S11-044.

02. The building plans include two Porte Cochere structures that are not shown on the revised DP/TP. The TP/DP will have to be revised prior to approval of the building plans. Contact Patricia Gehlen at 837-4919 for information on the revision process for S11-044. The revised TP/DP will also have to depict the development site as one lot due to the lot combo requirement.

03. A lot combo of the two lots that comprise this development will be required prior to approval of the building plans.

04. Zoning will review the building plans on the next submittal to ensure compliance with the revised TP/DP and lot combo documents.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Submit the building plans any requested documentation.
12/12/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07531

1. Provide a fault current analysis with AIC entries at the service entrance and each panel for determining appropriate bus ratings.

2. Provide 2012 IECC (interior) lighting calculation: provide ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
12/17/2014 LOREN MAKUS ENGINEERING REVIEW Denied A Development Package (grading) must be submitted and approved before the building plans can be approved by Engineering. The grading DP must be consistent with the last approved site DP.
12/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the water velocity in the proposed 2" water service pipe will not exceed the maximum velocity recommended by the manufacturer (i.e. 8 FPS). Reference: Section 303.2, IPC 2012.
2. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Verify that the pipe sizes called out for the flush valves (water closets and clinical sink) will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012.
4. The Watts model Cu7 double check valve is an obsolete product and does not have an ASSE listing. Provide a backflow protection device that is listed for the intended application. Reference: Sections 608.1 and 608.16.10, IPC 2012.
5. Appliances (e.g. ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012
6. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
12/19/2014 ROBERT SHERRY WATER REVIEW Completed
12/22/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
3. Show how the "Additional Efficiency Package Requirements" noted in Section C406, IECC 2012 is to be addressed. Reference: Section C401.2.1, IECC 2012.
4. Show that the mechanical systems for the building comply with the current energy code, e.g. provide the COMcheck Mechanical Compliance Certificate.
5. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project.
6. Show what provisions have been made for commissioning the mechanical building systems per Section C408.2, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2014 SHANAE POWELL REJECT SHELF Completed