11/13/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-18-14
Activity: T14CM07469
Address: 2510 N Goyette Ave #1, 2
Applicant: Michael Lyons

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide minimum 3/32" lettering per Unified Development Code.

SITE PLAN:
2. Indicate how electric will get from the service pole to the meter with a designated location of utility. Overhead service for new construction requires an appeal to the Building Official, IBC amendment section 112.1.1.

INCLUSIVE HOME DESIGN:
3. Provide an accessible route from the public way extending throughout the entire first floor (except for exempt areas as defined in section 1003.3), 1003.2. The elevation drawing or the site plan must show a ramped sidewalk if a paved driveway is not the accessible route.

FLOOR PLAN:
4. Specify which walls will be constructed with a one hour fire rating per detail on sheet A-7.

FOUNDATION PLAN:
5. Provide a floor or landing outside exterior doors, R311.3.

STRUCTURAL / FRAMING PLAN:
6. Specify the proposed wall bracing method with a complete braced wall line layout showing the location of braced wall panels within 10 feet of each end of each braced wall line and shall be no more than 20 feet apart, R403.1.6, R602.10.2.2.

ELEVATIONS:
7. Indicate the location of all parapets, crickets and scuppers as suggested by the section detail.
8. Specify overall height of building.

ELECTRICAL PLAN:
9. Provide an electrical riser diagram with grounding method and bonding to metallic piping E3607/8. Show an underground service entrance on the Riser Diagram or complete the Underground Electrical Service Wavier form.
10. Provide an equipment disconnect and convenience receptacles within 25' of mechanical equipment on the roof, E3901.12, E3903.4.
11. Specify faceplate grounding per E4001.11.1.
12. Specify tamper resistant receptacles per E4002.14.

OUTDOOR LIGHTING CODE
13. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.