Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07463
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/04/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide the design for the paint booth and the mix room. Include the exhaust flow rates, the duct sizes, the configuration of the exhaust termination, and the distance separating the exhaust termination from the property line, openings into the building, and air intakes. |
| 11/04/2014 | CLAYTON TREVILLYAN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 11/04/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/04/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/04/2014 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 11/04/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/04/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/04/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/04/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/09/2014 | KROBLES1 | APPROVAL SHELF | Completed |
| 12/09/2014 | KROBLES1 | OUT TO CUSTOMER | Completed |
| 12/09/2014 | KROBLES1 | REJECT SHELF | Completed |