Permit Number: T14CM07430
Parcel: 134112950

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM07430
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 5-11-15
Activity: T14CM07430
Address: 8109 E. Beverly
Applicant: Joe Romo

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Specify how water will be diverted from the existing building away from the proposed screen porch, R903.1.
2. Specify how rain water will be diverted out of screened porch or the weather protective method to keep it out of screen porch, R903.1.
3. Provide a cross section drawing of the screen wall enclosing the porch, R106.1.
4. Provide a floor or landing outside exterior doors, R311.3.
5. Justify the proposed 4x8 and 4x10 floor beams to support the structure as designed, R801.2.
6. Justify the proposed 4x6 roof beam to support the structure as designed, R801.2.
7. Provide details and dimensions for stairways that include the maximum riser height, minimum tread depth and handrail heights, R311.7.
8. Specify all hardware and hangers intended to support the proposed stairway and landing, R311.5.1.
9. Indicate the size and spacing of the proposed stairway and landing materials, R311.5.1.
10. Outlets located outside the kitchen area may not share the small appliance circuit, E3901.3.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2015 KROBLES1 OUT TO CUSTOMER Completed