Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07403
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/05/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | T14CM07403 1. Over 50% of suite area is altered, therefore remove exception notation on sheet E2. Provide 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination. a. Provide interior lighting control in compliance with C405.2.1.1. b. Provide interior lighting reduction control in compliance with C405.2.1.2. Ken Van Karsen Elect Plan Review PDSD, City of Tucson 520-837-4912 Kenneth.VanKarsen@tucsonaz.gov |
12/22/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/22/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
12/22/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/22/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/22/2014 | RSHERRY1 | WWM | REVIEW | Passed | No waste water plumbing |
12/22/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/22/2014 | ELEIBOL1 | ENGINEERING | REVIEW | Approved | |
12/22/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/23/2014 | CARL SCHULTZ | FIRE | REVIEW | Approved |