Permit Number: T14CM07391
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM07391
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Reprint sheets CNG-2.3, CNG-2.6, CNG-2.6, CNG-2.7, CNG-2.8, CNG-2.9, CNG-2.10, CNG-2.11, and CNG-3.4 so they are legible.
11/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the site plan that shows the extension of the CW service pipe and the 8" fire service pipe as note on 1/M-1.1.
11/13/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/13/2014 ROBERT SHERRY WATER REVIEW Completed
11/14/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.2; CODE NARRATIVE (CHAPTER 5): A STATEMENT IS MADE THAT THE ALLOWABLE BUILDING AREA IS 6750 SF PER TABLE 503. REVISE THE ALLOWABLE AREA TO THAT OF THE 2012 IBC.
2. SHEET A0.2; CODE NARRATIVE (CHAPTER 6); CODE REVIEW: THE CODE NARRATIVE INDICATES THE CONSTRUCTION TYPE IS IIA, WHILE THE CODE REVIEW TABLE INDICATES 2B. CLARIFY.
3. SHEET A0.2; CODE NARRATIVE (CHAPTER 7): REFERENCE IS MADE TO SECTIONS 708.1.4 AND 1017.1 FOR SEPARATING WALLS. REVISE THE SECTION NUMBERS TO THE 2012 IBC.
4. SHEET A0.2; CODE NARRATIVE (CHAPTER 10): THERE IS A REFERENCE TO TABLE 1016.1 FOR EXIT ACCESS TRAVEL DISTANCE. REVISE THAT TABLE NUMBER, AND REVISE THE DISTANCE LISTED (300 FEET) TO THE 2012 IBC.
5. SHEET A1.4; CHAIN LINK ELEVATION 5: SECTION 20/A8.0 IS CUT AT THE PIPE BOLLARD AND ALSO AT THE FENCE FOUNDATION. REVISE THE SECTION REFERENCE NUMBERS (NO SECTION 20 ON SHEET A8.0).
6. SHEET A2.0; WALL TYPES: IS THERE A WALL TYPE E3 INDICATED ON THE PLAN? VERIFY.
7. SHEET A2.0 (FLOOR PLAN); SHEET A4.0 (SECTION 1): SECTION 1/A4.0 IS CUT THROUGH THE ENTIRE BUILDING (GRIDS 1 THROUGH 4) ON THE PLAN, BUT SHEET A4.0 SHOWS THE SECTION CUT ONLY THROUGH A PORTION OF THE BUILDING. THEN SECTION 2/A4.0 1S CUT THROUGH THE REMAINDER OF THE BUILDING. CLARIFY.
8. SHEET A2.0 (FLOOR PLAN); SHEET A4.0 (SECTION 2): REVERSE THE DIRECTION OF THE SECTION CUT ON THE FLOOR PLAN.
9. SHEET A2.0 (FLOOR PLAN); SHEET A4.1 (SECTION 2): SECTION 2/A4.1 IS CUT OUTSIDE THE BUILDING AT THE SOUTHEAST CORNER. IS THIS CORRECT AT THAT LOCATION?
10. SHEET A2.0 (FLOOR PLAN); SHEET A4.1 (SECTION 4): THE TITLE OF SECTION 4 SHOULD BE NORTH WALL SECTION. VERIFY.
11. SHEET A2.0; FLOOR PLAN: THERE ARE SEVERAL SECTIONS (NORTH WALL OF SCADA ROOM, COMPRESSOR EQUIPMENT PAD, CNG PIPE RACK) THAT ARE NOT COMPLETE. REVISE.
12. SHEET A2.2; ROOF PLAN: AT THE EAST WALL, A SECTION 2/A2.2 IS CUT. HOWEVER, SECTION 2 INDICATES 'NOT USED'. CLARIFY.
13. SHEET A2.2; ROOF PLAN: A SECTION 13/A2.2 IS CUT AT A COMPRESSOR OPENING, BUT THE SECTION TITLE INDICATES 'EXHAUST FAN FLASHING'. CLARIFY.
14. SHEET A2.2; ROOF PLAN 1: ON THE NORTH END OF THE BUILDING, A NOTE INDICATES 'EXHAUST FANS-SEE MECH.'. REVISE THE NOTE TO REFERENCE THE ACCESS LADDER.
15. SHEET A3.0; EAST ELEVATION 1: A SECTION CUT ON GRID D AND A SECTION CUT BETWEEN GRIDS B AND C ARE NOT COMPLETE. REVISE.
16. SHEET A3.0; EAST ELEVATION 1: SECTION 20/A8.0 IS CUT NEAR GRID C. REVISE THE SECTION REFERENCE NUMBER (NO SECTION 20 ON A8.0).
17. SHEET A4.0; EAST WALL SECTION 1: AT THE TOP OF THE WALL, A SECTION 2/A2.2 IS INDICATED. HOWEVER, SECTION 2 INDICATES 'NOT USED'. CLARIFY.
18. SHEET A4.0; EAST WALL SECTION 1: AT THE SOFFIT, A SECTION 12/A2.2 IS INDICATED. HOWEVER, SECTION 12 INDICATES 'NOT USED'. CLARIFY.
19. SHEET A4.1; SOUTH WALL SECTION 2: AT THE 8'-0" WALL HEIGHT, A SECTION 12/A2.2 IS INDICATED. HOWEVER, SECTION 12 INDICATES 'NOT USED'. CLARIFY.
20. SHEET S-1.4 (LEDGER SCHEDULE); STRUCTURAL CALCULATIONS (SHEET 55): THE CALCULATIONS INDICATE A LEDGER SIZE OF MC10X6.5, WHILE THE SCHEDULE INDICATES AN ANGLE 6X3 1/2X5/16 (OR 1/4" BENT PLATE). CLARIFY.
21. SHEET S-2.0 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 24): THE CALCULATIONS INDICATE THE ROOF JOISTS AT 6'-0" O.C. (ALTHOUGH 7' SPACING WAS USED FOR THE LOADING), WHILE THE PLAN INDICATES A MAXIMUM 7'-0" O.C. CLARIFY.
22. SHEET S-2.0 (PLAN KEYNOTES NUMBER 4); SHEET S-3.0 (DETAILS 108, 109, AND 110): THE DETAILS INDICATE THE EQUIPMENT PAD HAS #4 AT 12" O.C. EACH WAY TOP AND BOTTOM (NOTE 4), WHILE KEYNOTE 4 ON THE PLANS INDICATES #5 AT 12" O.C. EACH WAY TOP AND BOTTOM. CLARIFY.
23. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/14/2014 DAVID RIVERA ZONING REVIEW Denied Zoning cannot approve the building plans until DP has been approved and all building plans reviewers have approved the building plan package.
11/17/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07391 Natural Gas Plant

1. Show the Plumbing and Mechanical clear zone notation appearing on plan #2/E2 onto sheet M-1.1.

2. Clarify the capacity of Panel G shown at the panel schedule and keynote #10/E3.

3. Clarify the location of keynote #9/E4.

4. Verify AIC rating of new panels is consistent with available fault current.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4912
Kenneth.VanKarsen@tucsonaz.gov
11/19/2014 KEN BROUILLETTE FIRE REVIEW Approved Spoke to Designer about the requirements in the 2012 IFC. He will resubmit plans and I will start review process following the resubmittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2014 CPIERCE1 REJECT SHELF Completed