Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM07372
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/13/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the access to the cleanout located within the crawl space. Relocate the cleanout if the crawl space is less than 24" in height. Reference: Section 708.4, IPC 2012. 2. Revise detail 3/p2 to show the location of the sediment trap to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2012. |
11/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
11/25/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/01/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM07372 1. Clarify inconsistent motor loads shown on the panel schedule and MAU wiring diagram. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/04/2014 | CPIERCE1 | REJECT SHELF | Completed |