Permit Number: T14CM07313
Parcel: 117132170

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07313
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/12/2014 ROBERT SHERRY WATER REVIEW Completed
12/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Reprint sheet P2.0 to make the plumbing schedule legible. [Initial comment: Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.]
2. Provide a cleanout for the 3" horizontal drain. [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012.]
12/12/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed