Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07313
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/12/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Reprint sheet P2.0 to make the plumbing schedule legible. [Initial comment: Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.] 2. Provide a cleanout for the 3" horizontal drain. [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012.] |
| 12/12/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/12/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |