Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07313
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
11/17/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Please provide site plan a floor level floor plan showing where this unit is to be located. 2. Please provide certification for special inspectors required. 3. Provide an accessible unit analysis of the building as to Type "A" and "B" accessible units. Define the type of unit this is to be and follow all requirements as per the 2009 ICC A117.1, Chapter 10. 4. Sheet A1.1 is missing. Please provide a Mezzanine floor plan and details. SHEET A1.0 5. Insure that the kitchen and toilet rooms meet all requirements of a type "A" or "B" accessible unit. 6. Door number 1 in in a rated partition. Is it a rated door assembly? SHEET A3.1 7. At detail 6, provide a vertical grab bar. SHEET S4.1 8. Please provide structural details and calculations for the 1 1/8" OSB mezzanine level deck and show how it is attached to the steel beams. 9. Provide structural calculations and details for the support of the suspended 47 gallon water heater. END OF REVIEW |
11/26/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Tucson Water limits a 2" meter to a maximum demand of 120 GPM but the water calculations indicate a total demand of 200 GPM. Verify the proposed demand and if the demand is 200 GPM, provide a larger water meter. |
11/26/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations for the suspended platform for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012. 2. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012. 3. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. 4. Clarify how the wide-mouth washer wall box is to accommodate both the washer discharge hose and the 1" water heater overflow drain. |
11/26/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the basis used for the design of the exhaust duct for the downdraft range hood (e.g. the manufacturer and model of the downdraft hood) and the required exhaust air flow rate. Reference: Section 304.1, IMC 2012 and footnotes b, f, and g with regard to kitchens, toilet rooms and bathrooms in private dwellings, Table 403.3, IMC 2012. 2. Provide calculations demonstrating how the ventilation rate was determined per Table 403.3, IMC 2012, for private dwellings. Reference: Section 403.2, IMC 2012. 3. Provide information to show that the terminations for the four exhaust systems comply with the requirements of Section 501.3.1 (3), IMC 2012. |
12/03/2014 | CPIERCE1 | WWM | REVIEW | Completed | |
12/03/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM07313 1. Electrical floor plan: a. show the location of panel 404L power source. b. clarify the location of the cooktop control circuit #18. c. show kitchen countertop receptacles within 2' of counter edges or corners and no more than 4' apart, 210.52(C)(1). d. show notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, 406.12. 2. Single line diagram: show panel 404L, feeder size and overload protection. 3. Panel schedule information: a. show the AIC rating of panel 404L. b. show GFCI protection for bathroom and kitchen countertop circuits, 210.8(A)(1) & (6). 4. Lighting fixture information: show notation requiring high-efficacy lamps for at least 75% of all lighting fixtures, IECC R404.1. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/11/2014 | KROBLES1 | APPROVAL SHELF | Completed |
12/11/2014 | KROBLES1 | OUT TO CUSTOMER | Completed |
12/11/2014 | CPIERCE1 | REJECT SHELF | Completed |