Permit Number: T14CM07271
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07271
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 2: SHEET T1; PROJECT SUMMARY: PER THE IBC SECTION 1014.2(4), EGRESS IN A GROUP M OCCUPANCY CAN PASS THROUH A STOCKROOM IF ITEMS 2.1, 2.2, 2.3, AND 2.4 ARE MET. ADDRESS THIS ISSUE. IT IS NOT CLEAR THAT ITEM 2.4 WAS ADDRESSED. VERIFY AND SHOW ON THE PLANS.
11/20/2014 BSTEVEN1 PLUMBING-COMMERCIAL REVIEW Approved
11/20/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07271

1. Plan: Show a 3 feet workspace in front of each electrical panel, E110.26 (A).

2. 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.
a. Provide interior lighting control in compliance with C405.2.1.1.
b. Provide interior lighting reduction control in compliance with C405.2.1.2.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov
11/20/2014 BSTEVEN1 MECHANICAL-COMMERCIAL REVIEW Approved