Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07271
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 2: SHEET T1; PROJECT SUMMARY: PER THE IBC SECTION 1014.2(4), EGRESS IN A GROUP M OCCUPANCY CAN PASS THROUH A STOCKROOM IF ITEMS 2.1, 2.2, 2.3, AND 2.4 ARE MET. ADDRESS THIS ISSUE. IT IS NOT CLEAR THAT ITEM 2.4 WAS ADDRESSED. VERIFY AND SHOW ON THE PLANS. |
11/20/2014 | BSTEVEN1 | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/20/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM07271 1. Plan: Show a 3 feet workspace in front of each electrical panel, E110.26 (A). 2. 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination. a. Provide interior lighting control in compliance with C405.2.1.1. b. Provide interior lighting reduction control in compliance with C405.2.1.2. Ken Van Karsen Elect Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
11/20/2014 | BSTEVEN1 | MECHANICAL-COMMERCIAL | REVIEW | Approved |