Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07271
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/28/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/28/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. 3. If the heat and moisture produced by the candy melter and the chocolate melter are not incorporated into the HVAC design for the suite, provide Type II exhaust hoods over the two appliances. If the HVAC system can accommodate the appliances, provide cooling load calculations and provide a minimum exhaust flow rate of 0.7 CFM /square foot for each appliance (each appliance shal1 be considered to occupy at least 100 square feet). Reference: Section 507.2.2, IMC 2012. |
10/28/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Rework electrical sheets so that font size is minimum 3/32" per C.O.T. standards |
10/28/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/28/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1; PROJECT SUMMARY: PER THE IBC TABLE 1015.1, TWO EXITS ARE REQUIRED FOR 52 OCCUPANTS. ADDRESS THIS ISSUE. 2. SHEET T1; PROJECT SUMMARY: PER THE IBC SECTION 1014.2(4), EGRESS IN A GROUP M OCCUPANCY CAN PASS THROUH A STOCKROOM IF ITEMS 2.1, 2.2, 2.3, AND 2.4 ARE MET. ADDRESS THIS ISSUE. 3. SHEET T1; APPLICABLE CODES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. 4. SHEET T1: INDICATE ON THE DRAWINGS THAT THE TRAVEL DISTANCE TO THE ACCESSIBLE RESTROOM FACILITIES MEET THE REQUIREMENTS OF THE IBC SECTION 2902.3.3. 5. SHEET A1; FLOOR/FIXTURE PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. 6. SHEET A1; FLOOR/FIXTURE PLAN: PER THE IBC SECTION 1109.11, SHOW ON THE PLAN AT THE PARTY ROOM THAT THE ACCESSIBLE SEATING REQUIREMENTS ARE MET. 7. SHEET A2; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. 8. SHEET A3; SECTIONS/ELEVATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. 9. SHEET A3; KEY TO ELEVATIONS: ELEVATIONS 1 AND 3 ARE REVERSED. VERIFY. 10. SHEET A3; KEY TO ELEVATIONS: ELEVATIONS 2 AND 4 ARE REVERSED. VERIFY. 11. SHEET A4; ELEVATIONS/LEGEND: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. 12. SHEET A5; SECTION 2: PROVIDE THE LATERAL BRACING SIZE AND SPACING ON THE SECTION. 13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
10/28/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/28/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012. 3. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. The pressure-absorbing devices shall conform to ASSE 1010; an air chamber is not acceptable. Reference: Section 604.9, IPC 2012. 5. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. 6. Appliances (e.g. chocolate melter) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 7. Provide an air gap discharge for the non-potable waste from the chocolate melter. Reference: Section 802.1.5, IPC 2012. 8. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 9. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 10. Provide accessible cleanouts in the island sink vent system to permit rodding of all portions of the vents located below the flood rim of the fixture. Reference: Section 916.3, IPC 2012. 11. Provide information to show that the proposed hydromechanical grease interceptor includes an integral flow control device. If not, install a vented, external flow control device per the manufacturer's instructions. Reference: Section 1003.3.5, IPC 2012. 12. The hydromechanical grease interceptor shall be directly-connected to the sanitary drain system. Reference: Section 301.3, IPC 2012. 13. Provide a cleanout for the section of the building sewer located immediately downstream of the gravity grease interceptor. Reference: Section 708.3.2, IPC 2012. |
10/28/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/28/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/19/2014 | AROMERO4 | WWM | REVIEW | Completed |