Permit Number: T14CM07238
Parcel: 105102430

Address:
585 E WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM07238
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Second comment: Provide the fixture unit calculations and the total water demand.] [Initial comment: Provide calculations showing how the water supply piping has been sized. Include all fixtures when calculating the total demand and determining pipe sizes. Reference: Sections 604.1 and 604.3, IPC 2012.]
01/05/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Second comment: The condensate drain is shown for the AHU serving the office; show all of the condensate drains. ] [Initial comment: Show the size, routing, and termination of the condensate drains. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.]
01/06/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/23/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved