Permit Number: T14CM07238
Parcel: 105102430

Address:
585 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07238
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2014 FRODRIG2 BUILDING-COMMERCIAL REVIEW Needs Review
12/18/2014 AROMERO4 WWM REVIEW Completed
12/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the fixture unit calculations and the total water demand. [Initial comment: Provide calculations showing how the water supply piping has been sized. Include all fixtures when calculating the total demand and determining pipe sizes. Reference: Sections 604.1 and 604.3, IPC 2012.]
12/18/2014 ROBERT SHERRY WATER REVIEW Completed
12/18/2014 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The condensate drain is shown for the AHU serving the office; show all of the condensate drains. [Initial comment: Show the size, routing, and termination of the condensate drains. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.]