Review Details: COMMERCIAL - TI
Permit Number - T14CM07238
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2014 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/18/2014 | AROMERO4 | WWM | REVIEW | Completed | |
| 12/18/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the fixture unit calculations and the total water demand. [Initial comment: Provide calculations showing how the water supply piping has been sized. Include all fixtures when calculating the total demand and determining pipe sizes. Reference: Sections 604.1 and 604.3, IPC 2012.] |
| 12/18/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/18/2014 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/18/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The condensate drain is shown for the AHU serving the office; show all of the condensate drains. [Initial comment: Show the size, routing, and termination of the condensate drains. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.] |