Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM07210
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/24/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Comment not resolved; the engineer is responsible for supplying this information before the building permit can be issued. [Initial comment: Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.] |
| 12/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Adding a note to the drawing does not change the fact that flat vents are being used with each floor sink installation; eliminate the flat venting. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (5 locations). Reference: Section 905.4, IPC 2012.] 2. If island venting is not being used in the design, remove detail 04/P-401 from the drawing set. The detail is incorrect as previously noted. [Initial comment: The use of an island vent (detail 04/P-401) is restricted to sinks and lavatories. Reference: Section 916.1, IPC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 01/14/2015 | CPIERCE1 | REJECT SHELF | Completed |