Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM07210
Parcel: 13419042D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07210
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2014 MARTIN BROWN FIRE REVIEW Approved
11/04/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-001; CODE INFORMATION: A REFERENCE IS MADE TO TABLE 803.5 FOR INTERIOR FINISHES. REVISE THE TABLE REFERENCE TO THE 2012 IBC.
2. SHEET G-001; OCCUPANCY LOAD: THE CALCULATED OCCUPANCY LOAD INDICATES 32 TOTAL OCCUPANTS. THE SEATING SUMMARY INDICATES A PROPOSED INDOOR SEATING OF 28, AND A PROPOSED OUTDOOR SEATING OF 21. THIS WOULD SUGGEST 49 OCCUPANTS (CUSTOMERS). IF THE ADDITION OF STAFF INCREASES THE TOTAL TO MORE THAN 49, THIS COULD AFFECT EXITING OR RESTROOM REQUIREMENTS. CLARIFY.
3. SHEET I-510; PLAN 1: SECTIONS A-A AND B-B ARE CUT ON THIS PLAN, BUT ARE NOT INDICATED ON THIS SHEET. VERIFY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/12/2014 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
11/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe sizes shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012.
2. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
3. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (5 locations). Reference: Section 905.4, IPC 2012.
4. The use of an island vent (detail 04/P-401) is restricted to sinks and lavatories. Reference: Section 916.1, IPC 2012.
11/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/21/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed