Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM07159
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2014 | RONALD BROWN | ADA | REVIEW | Approved | |
12/18/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
12/19/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Windows 2 and 3 along with door 1 are required to have NFRC product ratings or the default U-factors and default SHGC values must be used with COMcheck to demonstrate energy code compliance for the alterations to the building envelope. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3.(2), IECC 2012. Reference: Section C303.1.3, IEC 2012.] |
12/31/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed |